Magnetic Voltage Booster for three-phase LV distribution networks
Code: See Technical Characteristics
The Magnetic Voltage Booster (MVB) is a safe and reliable solution for three-phase LV power distribution networks, stabilizing and improving the voltage level in areas known to have voltage values below the normal limits, without high investment or major works, requiring one day for installation and commissioning.
Model |
MVB70-400 |
MVB160-400 |
MVB250-400 |
Distribution system connection |
TN / TT |
TN / TT |
TN / TT |
Frequency [Hz] |
50 |
50 |
50 |
Voltage [volts] (3 – phase) |
230/ 400 |
230/ 400 |
230/ 400 |
Load, nominal [kVA] |
30 |
70 |
112 |
Load, 6 hours, @20°C, input voltage 195 V [kVA] |
50 |
110 |
170 |
Current nominal [A] |
40 |
100 |
160 |
Current, 6 hours, @20°C, input voltage 195 V [A] |
70 |
160 |
250 |
Voltage set point [V] |
235 |
235 |
235 |
Voltage lift [%] (symmetrical loads) |
0…+15 |
0…+15 |
0…+10 |
Voltage lift, voltage reduction [%] (unbalanced loads) |
0…+28, 0…-7 |
0…+28, 0…-7 |
0…+18, 0…-7 |
Dynamic response [ms] 1 |
150 |
200 |
200 |
No-load loss [W] 2 |
180 |
220 |
220 |
Efficiency [%] |
97-99 |
97-99 |
97-99 |
Power factor [cos ϕ] 3 |
0,98-0,99 |
0,98-0,99 |
0,98-0,99 |
Total Harmonic Distortion [%] 3 |
1-5 |
1-5 |
1-4 |
Mechanical dimensions |
|
|
|
Width x Height x Depth [mm] |
754x928x539 |
1003x1190x648 |
1003x1190x648 |
Weight [kg] |
390 |
750 |
750 |
Cable connection (Copper) [mm] |
≤ 16 |
≤ 50 |
≤ 70 |
Oil filled [liters] |
75 |
158 |
158 |
Enclosure oil filled |
Galvanized |
Galvanized |
Galvanized |
Features |
|
|
|
Bypass @ U_out ±15% or high temperatures |
√ |
√ |
√ |
Handles 100% unbalanced load and maintains the voltage |
√ |
√ |
√ |
Single pole short circuit capacity increased by a minimum of 60% |
√ |
√ |
√ |
No moving parts in the power circuit |
√ |
√ |
√ |
Maintenance free |
√ |
√ |
√ |
25 years designed lifetime |
√ |
√ |
√ |
Quick installation < one day |
√ |
√ |
√ |
Option: SSP = Short-Circuit Safety Protection, 3-pole circuit breaker installed on output, FR3 = Environmental friendly organic oil.
1 – from zero voltage boost tofull voltage boost; 2- zero voltage boost; 3 – nominal load, varying voltage boosting