Intended use: earthing of electrical motors terminal or of their power supply cables.
Application: manual, in two ways:
Components:
Packing: waterproof bag
Technical characteristics |
Value |
||||||
Short-circuiting and earthing cable cross-section Sf Sp (mm2) |
16 |
25 |
35 |
50 |
70 |
95 |
120 |
Nominal short-circuit current for t = 1s Isc (kA) |
3,5 |
6 |
8 |
12 |
16 |
20 |
30 |
Shock (peak) nominal current for t = 0,02 s Isd (kA) |
8,75 |
15 |
20 |
30 |
40 |
50 |
75 |
Test short-circuit current for t = 1s (kA) |
4,6 |
6,9 |
9,2 |
13,8 |
18,4 |
23 |
34,5 |
Test shock (peak) current for t = 0,02 s (kA) |
11,5 |
17,25 |
23 |
34,5 |
46 |
57,5 |
86,25 |
Power factor (according for SR EN 61230) |
2,5 |
||||||
Short-circuiting cable length If (m) |
max. 2,5 |
||||||
Short-circuiting earthing cable length Ip (m) |
max. 7 |
||||||
Preferential dimension of fasteners |
M8 |
M8 |
M10 |
M10 |
M10 |
M12 |
M12 |
Optional dimensions of fasteners (mm) |
M10 |
M10 |
M8 M12 |
M8 M12 |
M8 M12 |
M10 M16 |
M10 M16 |
Components: