Single-phased earthing device for round conductors - classic clamp Cr
 
  
Code: Msp – Cr – Sp/lp – O
The single-phased earthing device is equipped with a classic phase clamp (“Cr” type) that can be fixed on round conductors in HV/MV substations. 
The “Cr” classic clamp contains an extruded body made of alluminium alloy and a tightening screw with a bayonet terminal for coupling with PMU insulating sticks.    
| Parameter | Value | ||||||
| Earthing cable section Sp (mm2) | 16 | 25 | 35 | 50 | 70 | 95 | 120 | 
| Nominal short-circuiting current for t = 1s Isc (kA) | 3,5 | 6 | 8 | 12 | 16 | 20 | 30 | 
| Nominal peak currrent for t = 0,02 s Isd (kA) | 8,75 | 15 | 20 | 30 | 40 | 50 | 75 | 
| Testing short-circuiting current for t = 1s (kA) | 4,6 | 6,9 | 9,2 | 13,8 | 18,4 | 23 | 34,5 | 
| Testing short-circuiting current for t = 0,02 s (kA) | 11,5 | 17,25 | 23 | 34,5 | 46 | 57,5 | 86,25 | 
| Maximum length of the earthing cable Ip (m) | 17,5 | 17,5 | 17,5 | 17,5 | 17,5 | 10 | 10 | 
| Peak factor | 2,5 | ||||||
| Conductor diameter on which the clamp can be applied (mm) | 17 ÷ 32 | ||||||
The single-phase earthing device contains the following components;
– classic phase clamp – 1 piece;
– earthing cable – 1 piece;
– earthing clamp – 1 piece;
The earthing device equipped with cables with 120 mm2 sections and lengths greater than 9,5 m is provided only with earthing lug (without earthing clamp).
The earthing device is delivered in sets of three pieces in a transport bag/box.