Main casing, basin (optional) and top-plate (PMS, PMD series)
Construction materials:
• orthophthalic polyester resin, reinforced with several layers of glassfibre matting
Characteristics:
• self-supporting structure reinforced at the points subject to greatest static and dynamic loads
• external surface protection via gel-coat resistant to UV radiation, cold and hot water, abrasion due to weathering and chemicals
• light-weight
• non-corroding
Fill pack (or heat exchange surface)
Construction materials:
• self-extinguishing PVC
Characteristics:
• 20 mm wide flute (air/water channels), especially suitable for industrial applications, reduced fouling, reinforced top layer (for the PMS, PMD series)
Multi-blade axial fan (for the PMS, PMD series)
Construction materials:
• hot-galvanized steel (electric motor support), fibreglass reinforced plastic (fan blades), stainless steel (fan screen grille)
Characteristics:
• high performance, low electrical power input
• directly driven by the electric motor
• constant safety, unaltered over time thanks to the fan grille
Dimensional elements:
A – Total height of tower
B, C – Length / Width of the cooling tower (horizontally)
D – Axis quota of inlet water pipe in tower towards the base of the tower
PMS cooling tower with basin
Type
|
A
[mm]
|
B
[mm]
|
C
[mm]
|
D
[mm]
|
Basin volume
[m3]
|
Weight [kg]
Empty In operation |
6/65
|
2110
|
800
|
800
|
1510
|
0,1
|
75
|
180
|
6/85
|
2595
|
1000
|
1000
|
1940
|
0,23
|
85
|
215
|
9/85
|
2595
|
1000
|
1000
|
1940
|
0,28
|
95
|
285
|
6/110
|
2800
|
1200
|
1200
|
2050
|
0,28
|
155
|
470
|
9/110
|
2800
|
1200
|
1200
|
2050
|
0,57
|
170
|
485
|
6/130
|
2860
|
1400
|
1400
|
2040
|
0,57
|
195
|
755
|
9/130
|
2860
|
1400
|
1400
|
2040
|
0,57
|
210
|
780
|
8/180
|
3140
|
1740
|
1740
|
2285
|
0,77
|
380
|
1380
|
10/180
|
3140
|
1740
|
1740
|
2285
|
0,77
|
410
|
1410
|
8/240
|
3380
|
2100
|
1900
|
2400
|
1,11
|
500
|
1800
|
10/240
|
3380
|
2100
|
1900
|
2400
|
1,11
|
525
|
1825
|
8/260
|
3450
|
2300
|
2100
|
2400
|
1,36
|
555
|
1955
|
10/260
|
3450
|
2300
|
2100
|
2400
|
1,36
|
580
|
1980
|
PMS cooling tower without basin
Type
|
A
[mm]
|
B
[mm]
|
C
[mm]
|
D
[mm]
|
Weight [kg]
Empty In operation |
6/65
|
1560
|
770
|
770
|
960
|
60
|
80
|
6/85
|
1895
|
980
|
980
|
1240
|
65
|
90
|
9/85
|
1895
|
980
|
980
|
1240
|
75
|
100
|
6/110
|
2140
|
1215
|
1215
|
1395
|
120
|
170
|
9/110
|
2140
|
1215
|
1215
|
1395
|
135
|
185
|
6/130
|
2080
|
1360
|
1360
|
1260
|
150
|
210
|
9/130
|
2080
|
1360
|
1360
|
1260
|
165
|
225
|
8/180
|
2275
|
1710
|
1710
|
1425
|
295
|
410
|
10/180
|
2275
|
1710
|
1710
|
1425
|
325
|
440
|
8/240
|
2330
|
2010
|
2010
|
1355
|
405
|
510
|
10/240
|
2330
|
2010
|
2010
|
1355
|
430
|
535
|
8/260
|
2400
|
2210
|
2210
|
1355
|
465
|
575
|
10/260
|
2400
|
2210
|
2210
|
1355
|
490
|
600
|