Water spraying nozzle - type DTCT
Code: see technical characteristics
The water spraying nozzles DTCT type are designed for cross flow cooling towers, with natural or forced draft, provided with water distribution tanks.
By mounting an elevator piece, can be ensured either the uniformity of irrigation in partial water flows or anti-frost protection of cross flow cooling towers.
The mounting of the DTCT spraying nozzles is made by simply introducing them in the holes on the floor of the distribution tanks.
Technical characteristics |
|
|
Code |
DTCT-P-“d”-170 |
DTCT-C-“d”-170 |
Working fluid |
water circulated through the cooling circuit |
|
Nozzle pressure (m. c. a.) |
0,2 ÷ 2 |
|
Air temperature (0C) |
– 30 ÷ +50 |
|
Water temperature (0C) |
+ 5 ÷ +80 |
|
Atmosphere |
with or without industrial emissions |
|
Nozzle outer diameter (mm) |
21÷ 40 |
|
Funnel inner diameter (mm) |
170 or 90 |
The water spraying nozzle DTCT type is composed of:
– funnel,
– nozzle,
– support with arms,
– disperser (various forms, depending on each application).