Application: from height – by direct connection (or by means of adaptors) of the short-circuiting device subassembly plugs to the sockets of the voltage connectors permanently mounted on ABC conductors.
Components:
Short-circuiting subassembly consisting of:
–Coupling plug for COT 10-95 A (ROMANIA) voltage connectors – „n” = 4…7 pieces
–Short-circuiting cable – 3…6 pieces
–Connecting cable to the earthing subassembly – 1 piece
Earthing subassembly consisting of:
-Coupling plug for connection to the short-circuiting subassembly – 1 piece
-Earthing cable – 1 piece
-Earthing clamp – 1 piece
Mobile earthing rod – 1 piece
Set of coupling adaptors to DPS* (ROMANIA) connectors – “n” – 4…7 pieces
Packing: waterproof bag
Technical characteristics | Value | ||
Rated operating voltage Un (kV) | max. 1 | ||
Short-circuiting and earthing cable cross-section Sf, Sp (mm2) | 16 | 25 | 35 |
Nominal short-circuit current for t = 1 s Isc (kA)* | 4 | 6 | 8 |
Shock (peak) nominal current for t = 0,02 s Isd (kA) | 8 | 12 | 16 |
Test short-circuit current for t = 1 s (kA) | 4,6 | 6,9 | 9,2 |
Shock (peak) current for t = 0,02 s (kA) | 9,2 | 13,8 | 18,4 |
Power factor (according to SR EN 61230) | 2 | ||
Phase cable length If (m) | max. 1 | ||
Earthing cable length Ip (m) | max. 15 | ||
Number of coupling plugs to ABC conductors | max. 7 |
* NOTE = for DPS connectors, adapters provide nominal short-circuit current for t=1 s – max. 6 kA
Components:
The short-circuiting subassembly consisting of:
The earthing subassembly consisting of: