Intended use: MV overhead line conductors placed maximum 10,5 m from the ground
Application: from the ground, by hanging the self-locking clamps mounted at the end of metallic telescopic sticks on overhead conductors, using the insulating stick included in the short-circuiting device.
Benefits: easy to be assembled and applied by a single user.
Components:
Packing: waterproof bag.
Tips: the absence of voltage on overhead conductors is checked using the subassembly consisting of the self-locking clamp – metallic telescopic stick, with a medium voltage detector fixed in the special part at the end of the insulating stick, consisting of two modules.
The voltage detector is not included in the product set.
Technical characteristics | |
Earthing cable cross-section / length (mm2/m) | 35/10 |
Nominal short-circuit current for t=1s Isc (kA) | 8 |
Shock (peak) nominal current for t=0,02s Isd (kA) | 20 |
T est short-circuit current for t=1s (kA) | 9,2 |
Test shock (peak) current for t=0,02s (kA) | 23 |
Power factor (according to SR EN 61230) | 2,5 |
Length of the telescopic metallic stick – folded/extended (m) | 2,45/6,35 |
Total length of the insulating stick consisting of two modules (m) | 3,42 |
Diameter of the conductor where the phase clamp can be applied (mm) | 4÷22 |