Application: from the ground, by mounting the phase clamp on the conductor, followed by the tightening of the clamp driving screw.
Classic / automatic phase clamps must be handled using an insulating stick according to the voltage of the installation, provided with “RO bayonet’’ coupling system.
Constructive shapes: three-phase.
Constructive types of phase clamps:
Three-phase short-circuiting device consists of:
Packing: waterproof bag.
Related products:
– Multipurpose modular insulating stick type PMU 20-1 B/ba / PMU 110-2 B/ba / PMU 220-2-B/ba / PMU 400-3-B/ba
| General technical characteristics of short-circuiting devices with universal clamp types CCU, CAU and CARU | |||||||
| Earthing cable cross-section Sp (mm2) | 16 | 25 | 35 | 50 | 70 | 95 | 120 | 
| Nominal short-circuit current for t = 1s Isc (kA) | 4 | 6,25 | 8,75 | 12,5 | 17,5 | 23,75 | 30 | 
| Shock (peak) nominal current for t = 0,02 s Isd (kA) | 10 | 15,63 | 21,9 | 31,25 | 43,75 | 59,38 | 75 | 
| Test short-circuit current for t = 1s (kA) | 4,6 | 7,2 | 10,06 | 14,38 | 20,13 | 27,31 | 34,5 | 
| Test shock (peak) current for t = 0,02 s (kA) | 11,5 | 17,97 | 25,16 | 35,94 | 50,31 | 68,3 | 86,25 | 
| Power factor (according to SR EN 61230) | 2,5 | ||||||
.
| Phase clamp type | Classic universal clamp (CCU) | Universal automatic clamp (CAU) | Universal automatic fast clamp(CARU) | 
| Short-circuiting cable length – three-phase short-circuiting device lf (m) | max 1,5 | max 1,5 | max 1,5 | 
| Earthing cable length three-phase short-circuiting device lp (m) | max. 8.5 | max. 8.5 | max. 8.5 | 
| Thickness of the flat bar where the phase clamp g can be mounted g (mm) | max. 40 | max. 37 | max. 40 | 
| Diameter of the sphere-type coupling part Sf (mm) | 30 | 30 | 30 | 
| Diameter of the conductor where the phase clamp can be applied øD (mm) | 9 ÷ 32 | 9 ÷ 32 | 9 ÷ 32 | 
Three-phase short-circuiting device consists of:
Related products:
– Multipurpose modular insulating stick type PMU 20-1 B/ba / PMU 110-2 B/ba / PMU 220-2-B/ba / PMU 400-3-B/ba