Application: from height – by hanging the self-tightening clamp to the conductor followed by the pulling down of the clamp.
Components:
-Short-circuiting subassembly provided with:
-Self-tightening clamp with insulating stick – “n” = 4 … 7 pieces
-Short-circuiting cable – 3 … 6 pieces
-Connection cable to the earthing subassembly provided with socket plug – 1 piece
Earthing subassembly consisting of:
-Coupling plug for the connection to the short-circuiting subassembly – 1 piece
-Earthing cable – 1 piece
-Earthing clamp – 1 piece
Insulating extension stick – 1 piece
Mobile earthing rod – 1 piece
Packing: waterproof bag
Packing: waterproof bag
Technical characteristics |
Value |
|
Rated operating voltage Un (kV) |
max. 1 |
|
Short-circuiting and earthing cable cross-section Sf, Sp (mm2) |
16 |
25 |
Nominal short-circuit current for t = 1s Isc (kA) |
4 |
6 |
Shock (peak) nominal current for t = 0,02 s Isd (kA) |
8 |
12 |
Test short-circuit current for t = 1s (kA) |
4,6 |
6,9 |
Shock (peak) nominal current for t = 0,02 s (kA) |
9,2 |
13,8 |
Power factor (according to SR EN 61230) |
2 |
|
Phase cable length lf (m) |
max. 1 |
|
Earthing cable length lp (m) |
max. 15 |
|
Number of self-tightening clamps / adaptors for DPS connectors (n) |
max. 7 |
|
Protection length of the insulating stick (m) |
0,35 |
|
Total protection length of the stick, with the extension piece (m) |
0,84 |
|
Conductor diameter where the phase clamp can be applied (mm) |
5 – 16 |
|
Conductor cross-section where the phase clamp can be applied (mm2) |
25 – 120 |
Components:
The short-circuiting subassembly is provided with:
The earthing subassembly consisting of: