ESE lightning conductor Franklin France - Active 2D type
ESE lightning conductor type Active 2D®,
The effectiveness of a lightning conductor does not depend only on the excitation time of a leader to the rod.
The operating principle of the Saint Elme Active 2D® consists, not only to initiate the upward leader, but moreover, provides enough energy to ensure its propagation until the junction with the downward leader:
Characteristics of Saint Elme Active 2D® lightning conductor:
– Solar (2) or wind (1) energy for the power device
– Atmospheric electrical field for the impulse device.
The Saint Elme Active 2D® lightning conductor was tested in the high voltage laboratory Bazet (CEB) in compliance with the NF C 17-102 standard, and is subject of tests campaign in situ.
The Saint Elme Active 2D® lightning conductor can be tested on site with his remote control tester.
Simple and fast, the test does not require any particular operation of lightning conductor dismounting and can be done safety from the ground.
Active 2D® remote control testers use the communication by Radio waves, and create any electromagnetic perturbation.
Saint Elme Active 2D® lightning conductors and their testers are both equipped with one transmitter / receiver: bi-directional emission and reception.
Type |
Active 2D 30 |
Active 2D 60 |
||||||
Excitation advance |
ΔT = 30 µs |
ΔT = 60 µs |
||||||
Protection level |
I |
II |
III |
IV |
I |
II |
III |
IV |
Hinstall (m) |
Rp (m) |
Rp (m) |
||||||
2 |
19 |
21 |
25 |
28 |
31 |
34 |
39 |
43 |
3 |
29 |
33 |
38 |
43 |
47 |
52 |
58 |
64 |
4 |
38 |
43 |
51 |
57 |
63 |
69 |
78 |
85 |
5 |
48 |
55 |
63 |
71 |
79 |
86 |
97 |
107 |
6 |
48 |
55 |
64 |
72 |
79 |
87 |
97 |
107 |
8 |
49 |
56 |
65 |
73 |
79 |
87 |
98 |
108 |
10 |
49 |
57 |
66 |
75 |
79 |
88 |
99 |
109 |
20 |
50 |
59 |
71 |
81 |
80 |
89 |
102 |
113 |
30 |
50 |
60 |
73 |
85 |
80 |
90 |
104 |
116 |
60 |
50 |
60 |
75 |
90 |
80 |
90 |
105 |
120 |
Hinstall = mounting height, compared to the highest point (elevation) of the building
Rp = radius of protection, depending on the mounting height and the level of protection