The portable single-phase short-circuiting device with extruded automatic phase clamp (type CAEr) is used on round conductors in substations.
The extruded automatic phase clamp (CAEr) has an extruded aluminium-alloy body and a clamping screw with a bayonet coupling at one end for connection to the insulating stick.
|
Parameter |
Value |
||||||
|
Earthing cable cross-section S p (mm2) |
16 |
25 |
35 |
50 |
70 |
95 |
120 |
|
Rated short-circuit current for t = 1s I sc (kA) |
3,5 |
6 |
8 |
12 |
16 |
20 |
30 |
|
Rated peak current for t = 0,02 s I sd (kA) |
8,75 |
15 |
20 |
30 |
40 |
50 |
75 |
|
Short-circuit test current for t = 1s (kA) |
4,6 |
6,9 |
9,2 |
13,8 |
18,4 |
23 |
34,5 |
|
Peak test current for t = 0,02 s (kA) |
11,5 |
17,25 |
23 |
34,5 |
46 |
57,5 |
86,25 |
|
Maximum earthing cable length I p (m) |
17,5 |
17,5 |
17,5 |
17,5 |
17,5 |
10 |
10 |
|
Power factor |
2,5 |
||||||
|
Conductor diameter accepting the phase clamp (mm) |
17 ÷ 32 |
||||||
|
Earthing connection method |
With manual earthing clamp * For cross-sections of 120mm 2 and lengths greater than 9,5m, only an earthing lug is fitted (without a manual earthing clamp) |
||||||
The single-phase short-circuiting device includes:
- extruded automatic phase clamp – 1 piece;
- earthing cable – 1 piece;
- earthing clamp – 1 piece.
The short-circuiting devices are supplied in sets of 3, in a carrying bag/case.
- Chestionar_alegere_scurtcircuitor_Romind_TG37.pdf
- Certificat_de_Conformitate_nr._1110-04_.05_.2006_.1_(2)_.pdf
- Adresa_2988_Certificat_Conformitate_1110.pdf
- Fisa_scurtcircuitor_monofazat_pentru_conductori_rotunzi_-_clema_automata_extrudata.pdf
- Single-phased_earthing_device_for_round_conductors-automatic_clamp_CAEr.pdf
- Adresa_prelungire_2014_scurtcircuitor_conductori_rotunzi_cleama_CAEr_.PDF