The CC-162-K voltage detector for capacitive test points on separable connectors in indoor and outdoor electrical installations is used on high-voltage connection terminals incorporating a capacitive divider.
These devices detect absence of voltage according to the detection and internal safety principles defined in IEC 61243-1.
The installation voltage must fall within the range shown on the detector housing, namely 3 ÷ 36 kV.
Use the voltage detector in dry weather with an insulating stick suitable for the installation voltage and operating conditions.
The CC-162-K has a white polycarbonate housing with excellent mechanical and dielectric properties and a universal coupling. A hexagonal adaptor is supplied for use with telescopic insulating sticks with a hexagon 12 socket coupling.
The indication and control panel includes:
– the test button for the integrated checking device, which checks operation of the electronic circuit;
– buzzer for audible voltage-presence indication;
– LED-uri in different colours ( red (1) – voltage presence; green (1) – standby status).
Checking absence of voltage
Connect the voltage detector to an insulating stick suitable for the installation. Perform the self-test. Remove the protective cover from the voltage test point using the detector extension. Bring the detector electrode into contact with the voltage test point.
Voltage presence is indicated by:
– a flashing LED red , together with an intermittent audible buzzer signal.
When voltage is absent, the LED green remains lit, with no other optical (red LED) or audible indications.
Perform another self-test at the end of the operation.
The voltage detector is supplied in a carrying bag with shock-protective elements.
Other required equipment:
PTU 20-45-C telescopic insulating stick with hexagon 12 coupling
| Technical characteristics | |
| Rated operating voltage (kV) | 3 ÷ 36 |
| Frequency (Hz) | 50 / 60 |
| Operating temperature range ( 0C) | -25 …+55 |
| Power supply – alkaline battery | 9 V type 6LR61 |
| Maximum humidity | 96 % |
| Length (mm) | 265 |
| Detector weight including battery and adaptor (kg) | 0,47 |