Earthing devices for MV / HV overhead and underground lines
Portable earthing and short-circuiting devices (commonly referred to as “earthing devices“) are protective equipment used to temporarily earth and short-circuit the conductors of an electrical installation. The use of earthing devices is the main preventive measure protecting personnel against electrical risk in the event of voltage accidentally appearing in the work area.
Earthing devices must always be installed by two electricians, in the following sequence of operations:
Earthing the device, by firmly attaching the earth clamp (CLP) or the lug of the earthing cable to the artificial / natural earth electrode of the electrical installation or to the portable earth electrode (commonly called the earth “spike” of the device), previously driven into the ground;
Verifying the absence of voltage on the conductors to be earthed / short-circuited, using a voltage detector;
Attaching the phase clamps (CLF) of the device, which actually makes the temporary electrical connection between the phase conductor and the earth electrode through the component parts of the device.
Depending on the type of device and the voltage of the installation, the phase clamps must be attached to the conductors of the electrical installation using insulating sticks, handles or other insulating devices designed specifically for this operation.
Standards, configurations and cables
The earthing devices are manufactured in accordance with SR EN 61230 in various configurations – single-phase, three-phase or multi-phase – and can be used in both indoor and outdoor electrical installations. The short-circuiting and earthing cables can be connected in various configurations, as required.
The central junction of three-phase earthing devices is available in two designs: a central joint insulated with black heat-shrink tubing, or a connection block covered by a red insulating housing that allows the junction to be inspected.
The short-circuiting and earthing cables are made of highly flexible, class 6 stranded copper in accordance with SR EN 60228 and are protected by a transparent plastic insulating sheath extruded directly onto the stranded conductor, in accordance with SR EN 61138.
Phase clamps (CLF) and earth clamps (CLP)
Phase clamps (CLF) and earth clamps (CLP) are designed and manufactured in a wide range of shapes so that they can be applied to different types of conductors in LV, MV and HV electrical installations and provide the mechanical strength needed to withstand an incident caused by voltage unexpectedly appearing in the installation.
Although it may seem less important, choosing the right phase and earth clamps allows the user to apply the earthing device more ergonomically and, at the same time, in complete safety in terms of electrical protection.
Fastening methods
Phase and earth clamps are fastened to the installation conductor or to the earthing bar by various methods:
Screw clamping: the installation conductor is gripped firmly between the clamp body and the movable jaw driven by a screw (an operation that may be preceded by pre-positioning the clamp on the conductor). In this case, the clamping force on the conductor is provided by the manual tightening torque applied to the clamp’s operating screw.
Spring clamping: the installation conductor is gripped between the clamp body and the movable jaw driven by a spring or other elastic system. In this case, the clamping force on the conductor depends directly on the characteristics of the spring and the dimensions of the conductor.
Clamping by shape and weight (self-clamping): the clamping force on the conductor is determined directly by the weight of the assembly formed by the phase clamp and the earthing conductor.
End fittings for operating screws
On phase and earth clamps with an operating screw, the screw can be fitted with various end fittings, allowing the clamp to be coupled to and operated with other devices (usually insulating sticks) or operated by hand:
Screw-clamping phase clamps are mainly fitted with “RO bayonet” heads, which can easily be coupled to and uncoupled from the “RO bayonet” coupling systems of insulating sticks.
Optionally, phase clamps can also be supplied with other screw end fittings, such as: “DIN bayonet” (a system similar to the “RO bayonet” but with different dimensions), “12 mm hexagon” (for operation with a stick fitted with a hexagonal coupling system), “eye” (for operation with a hook-type part) or “insulated handle” (for manual operation).
Earth clamps — since they are attached by hand to the earthing strip or to similar elements — are mainly fitted with screws with a sliding “tommy bar” or with an “insulated handle”.
Design categories
Screw-clamping phase clamps come in two design categories: “classic” and “automatic”:
“Classic” screw-clamping clamps have a simple operating screw that moves the jaw and tightens the clamp on the conductor.
“Automatic” screw-clamping clamps have a system of levers and springs that moves the jaw automatically when the clamp touches the conductor to which it is to be fastened, pre-positioning the clamp on the conductor. After this step, the clamp must be tightened firmly on the conductor by turning the screw and locking the jaw in position.
Spring-clamping and self-clamping clamps can also be classed as “automatic” clamps since, once they are hooked or pushed onto the conductor of an LV / MV / HV overhead line, the conductor remains held between the jaw and the clamp body.
Clamp applications
Depending on the type of installation and the shape of its conductors or busbars, phase clamps are designed and sized so that they can be applied simply and safely to:
bare conductors of LV, MV or HV overhead lines;
bars or parts with a rectangular cross-section (clamps for flat bars);
bars or parts with a round cross-section (clamps for round bars);
ball points of various sizes;
bars of various shapes or orientations (universal clamps);
terminal parts of installations of various shapes or purposes (encapsulated terminals, bases for insulation-piercing clamps, MPR fuse bases, plug-in separable connectors, various types of voltage connectors, T-connectors, ball points, etc.).
Earth clamps connect the earthing devices directly to the fixed natural or artificial earth electrodes of the electrical installation or to the portable earth electrode (the earth “spike” of the device). They are made in several shapes and sizes, depending on the rated short-circuit current that the earthing device must carry and on the shape and dimensions of the earthing element.
Earth clamps are generally manual clamps (attached directly by hand to the earthing element). They may have a “classic” (vice-type) design or be fitted with a “scraping jaw”. When applied and tightened, manual earth clamps with a scraping jaw remove layers of oxide, dirt and protective paint down to the bare metal, giving an adequate contact resistance. Earth clamps also include special-purpose clamps, for example those for railway rails.
Packaging, environmental conditions and low-voltage versions
Earthing devices can be packed in:
bags of various sizes made of waterproof material suited to the operating conditions;
plastic boxes (available on request);
painted sheet-metal boxes (only for some models of earthing devices for MV lines).
The operating temperature range of portable earthing and short-circuiting devices is –25 °C … +55 °C, and the relative humidity can be up to 100%.
Recommendations for choosing earthing devices
Unlike other manufacturers and sellers of earthing devices, Romind gives you the option of buying products tailored to your technical requirements and operating conditions. For almost all products in this category, you can select a technical configuration that matches your needs as closely as possible. What is more, you can choose the models of phase and earth clamps, how the cables are connected between the clamps, and the cable lengths and cross-sections, so that the final product is fully adapted both to the technical requirements of the installation and to your preferences. As long as you know the points in the installation where the earthing devices will be fitted, you can set the lengths of the phase and earthing cables yourself and choose the appropriate cable cross-section for the short-circuit current to be carried. Then, according to your preferences, you select one of the phase clamps suited to the conductor on which the clamp will be fitted (classic / automatic) and, likewise, one of the available earth clamps.
For earthing devices for LV overhead networks, you can also select the number of phase clamps (usually between 4 and 7) to suit the installation where the device will be fitted, so you avoid buying a product that does not match your specific conditions.
For earthing devices for MV overhead networks, depending on how you wish to apply the device (from the ground or at height – from an aerial platform or from the pole), you can select a model suited to the installation conditions, with or without an insulating stick for applying it. Also, if you already own a particular model of stick with a particular coupling system, you can choose or request clamps or installation/removal accessories adapted to your stick, without having to buy a new one.
If you want an earthing device that can be fitted at several points in different installations, on several types and shapes of conductors, select one of the universal clamps in the Romind range as the phase clamp; these clamps can be applied to flat-strip conductors, stranded (round-section) conductors and ball points. For each phase or earth clamp you choose, check the dimensions and shape of the conductors it can be applied to, as well as the short-circuit current it is rated for.
If you need a product configuration that you cannot find on the website or in the catalogue, we recommend that you call us so that we can understand your needs and find a suitable technical solution together.
Portable earthing devices for MV overhead lines
are three-phase, fitted with self-clamping / self-locking clamps (CAA), and are made in various versions so that the phase clamps can be attached to the overhead line conductors from the ground or at height (from the pole or from an aerial platform).
Portable earthing devices for HV overhead lines
are single-phase, fitted with automatic self-locking clamps (CAA), and are applied from the metal cross-arms of the towers using insulating sticks suited to the installation voltage.
Portable continuity and equipotential bonding devices for work on insulated MV cables are a means of protection against voltage accidentally appearing at the workplace and serve to delimit the work area.
Portable equipotential bonding devices for work on MV overhead lines are a means of protection used to bring work machinery/ equipment to the same potential as elements of an overhead line.