The insulating mats are made of 3 mm-thick rubber sheets and are widely used as supplementary electrical protective equipment in indoor low-voltage installations.
Insulating mats are frequently used on floors in substations, power plants, motor rooms, electrical cabins and industrial premises.
Insulating mats are used together with one or more insulating protective devices, such as insulating gloves, boots or sticks.
The blankets are secured with insulating clamps (available on request) to prevent accidental detachment from live parts.
| Technical characteristics according to IEC 61111:2009 | |
| Mechanical puncture resistance | YES |
| Anti-slip performance verification | YES |
| Dielectric testing according to class | YES |
| Mechanical puncture resistance after ageing | YES |
| Mechanical folding resistance after exposure to low temperatures | YES |
| Flame retardance | YES |
| Oil resistance | YES |
| Acid resistance | YES (category A) |
| Ozone resistance | YES (category Z) |
| Technical characteristics | |
| Maximum operating voltage (V AC) | 1.000 |
| Test voltage (V AC) | 5.000 |
| Withstand voltage (V AC) | 10.000 |
| Roll length (m) | 10 |
| Hardness (Sh A) | 65 +/- 5 |
| Weight (kg/m2) | 3,3 |
| Standard width (mm) | 1.000 |
| Optional width (mm) | 1.200 |
| Surface finish | smooth / ribbed (anti-slip) |