The insulation-piercing clamp for insulated conductors (ENEL model) is intended to prepare insulated low-voltage conductors in distribution boards and transformer substations for short-circuiting and earthing. It is designed and manufactured according to ENEL technical specification EA 0138 RO.
The clamp body consists of two insulating, flame-retardant and weather-resistant parts. The piercing rod has an external 8 mm-diameter hole for connecting the phase clamps of the short-circuiting device. As it carries current between the cable and the short-circuiting device, it is made of tin-plated copper alloy. Fasteners are stainless steel.
|
Parameter |
Value |
|
Rated operating voltage U n (kV) |
max. 1 |
|
Rated short-circuit current for t = 0,2 s I sc (kA) |
8 |
|
Operating temperature range (OC) |
-25...+ 55 |
The following variants are available, depending on the cross-section of the LV conductors:
|
Code |
1MP138/10 |
1MP138/20 |
1MP138/30 |
1MP138/40 |
|
Conductor cross-section (mm 2) |
10 - 25 |
35 - 70 |
95 - 150 |
150 - 240 |
|
Identification cap colour |
Violet |
Green |
Orange |
Black |